Remedial adaptive topology control (RATC)
Evaluate power system to recommend switching actions that will alleviate flow
on specified branch by calculating a set of Line Outage Distribution Factors (LODF)
and applying them to the solved flows
The algorithm works as follows:
- Fabricate and place 100MW flow across selected branch
- Solve flows for fabricated case
- Calculate fraction of flow in target branch
- Assign remaining fracction to network, NF
- LODF for each Line (branch, actually), = flow / 100 / NF